Pro Refrigeration NT LLC

Unit was not making ice when I arrived. I noticed some boxes stacked on the unit next to the ice machine blocking airflow to the condenser. I removed the boxes and the pressure dropped to near 315psi. This is still high so I checked the condenser coil and found it very dirty. I blew it out with nitrogen and the pressure dropped below 300. The pressure looked good throughout and it dropped ice in 22 minutes on 2/24/24 in Farmers Branch Texas.