On 11/07/2022 Unit was showing very low head pressure at low ambient temps. I topped the system off and did a leak check. I found no leaks but I did notice that there is no fan cycle switch on this dual fan system. When I disconnected power to one of the fans the pressures leveled out. I recommend a switch be added to the system for proper function during fluctuations in ambient temp in Desoto Texas.

Near Falcon Dr Desoto Texas 75115