Glycol Chiller Had Bad Capacitor

Glycol chiller had bad capacitor. Replaced capacitor and installed customer provided discharge bypass valve on 8/20/24 in McKinney Texas. Near Majesty Drive, Dallas, TX 75247 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Hot Well Not Heating

Hot well not heating. Located hot well tested voltage found no power. Traced power back to a sub panel found breaker tripped rest breaker and unit heating on 8/18/24 in McKinney Texas. Near West University Drive McKinney, TX 75070 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Found High Head Pressure Alarm

Found high head pressure alarm. Pulled condenser screen and found it was totally clogged. Cleaned and put back in place. No further issues at this time on 8/16/24 in Plano Texas. Near West Parker Road Plano, TX 75023 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Two Drawer Line Cooler Icing Up

Two drawer line cooler icing up. Performed diagnostics and found thermostat was set at its coldest point causing unit to ice up. Adjusted thermostat on 8/15/24 in Garland Texas. Near Broadway Blvd Garland, TX 75043 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Found WIC Condensate Pan Overflowing

Found WIC condensate pan overflowing. Unclogged drain pan, checked Temperature across evap. and made sure it was 20 below, all ops normal at this time on 8/13/24 in Richardson Texas. Near N Central Expressway Richardson, TX 75080 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Reach-In Cooler Making Noise

Reach in cooler making noise and not holding temp. Found built up in drain pan and fan motor unable to spin due to ice. Cleared drain with nitro installed drain pan tabs to help with preventing future clogging on 8/12/24 in Dallas Texas. Near Lemmon Ave Dallas, TX 75219 Check out the Areas We Serve […]

Ice Machine Door Switch not Activating

Ice machine door switch not activating due too door not properly placed after customer cleaned unit. Adjusted door and door switch, started unit up verified operation on 8/11/24 in Frisco Texas. Near Main St Frisco, TX 75033 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Removed Existing Suction Line Drier

Removed existing suction line drier, brazed 1 coupling with a 2 ft long straight 3/4 copper tube and Pulled vacuum to under 500 microns. Charged system with 15 pounds of 404A. Watched 3 batches of ice drop on 8/9/24 in Tyler Texas. Near Towne Crossing Boulevard Mesquite, TX 75150 Check out the Areas We Serve […]

Reach in Cooler had a Dirty Condenser Coil

Reach in cooler had a dirty condenser coil as well as a scrambled PCB board due to infestation, unit comes on and off but not reaching set temp. I managed to clean coils and clean board with contact cleaner. Started unit and unit reaching colder temps on 8/8/24 in Tyler Texas. Near S Broadway Ave […]

Installed New Motor

Installed new motor, while removing motor found only one bolt was holding entire motor mount bracket as well as no key ways in motor shaft or hub. Verified operation normal at this time on 8/6/24 in Dallas Texas. Near N Central EXPY Dallas, TX 75201 Check out the Areas We Serve and jobs we are […]