Replace Reach-In Cooler Compressor

Replace Reach-In Cooler Compressor, removed old compressor brazed new one in, pulled vacuumed and charged unit with r290. Started unit up verified operation all ops normal at this time on 8/30/24 in Dallas Texas. Near Doric Cir Dallas, TX 75220 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Installed New Blower Relay

Installed new blower relay, started unit up verified operation all ops normal at this time on 8/29/24 in Dallas Texas. Near Park Lane Dallas, TX 75225 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Condenser Filter Clogged

Condenser filter clogged which explains why evaporator was frozen over. Cleaned coil and defrosted unit started unit up and unit immediately dropped to 34 degrees on 8/28/24 in Tyler Texas. Near S Broadway Ave Tyler, TX 75703 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Replaced Ice Machine Proximity Sensor

Replaced ice machine proximity sensor, started unit up verified operation all ops normal at this time on 8/26/24 in Van Texas. Near South Oak Street Van, TX 75790 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Replaced Failed Condensate Wicking Pads

Replaced failed condensate wicking pads, removed back panel turned cooler off removed old wicking pads replaced with new wicking pads replaced back panel turned cooler on working as should be on 8/23/24 in Dallas Texas. Near Eldorado Parkway McKinney Texas 75070 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ […]

Repaired Leak on RTU

Repaired leak on RTU. Replaced filter drier and TXV, and tested for leaks, found no more leaks. Pulled vacuum to under 500 microns and recharged system with 8 pounds of 407A on 8/22/24 in Dallas Texas. Near Greenville Ave Dallas, TX 75206 Check out the Areas We Serve and jobs we are doing by clicking […]

Found Supply Duct Dropped

Found supply duct dropped, as well as a large leak on plenum. Was able to secure duct work and seal up plenum to make repairs on 8/21/24 in McKinney Texas. Near Park Lane Dallas, TX 75225 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Glycol Chiller Had Bad Capacitor

Glycol chiller had bad capacitor. Replaced capacitor and installed customer provided discharge bypass valve on 8/20/24 in McKinney Texas. Near Majesty Drive, Dallas, TX 75247 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Hot Well Not Heating

Hot well not heating. Located hot well tested voltage found no power. Traced power back to a sub panel found breaker tripped rest breaker and unit heating on 8/18/24 in McKinney Texas. Near West University Drive McKinney, TX 75070 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Found High Head Pressure Alarm

Found high head pressure alarm. Pulled condenser screen and found it was totally clogged. Cleaned and put back in place. No further issues at this time on 8/16/24 in Plano Texas. Near West Parker Road Plano, TX 75023 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]