Condenser Filter Plugged with Debris
Condenser filter plugged with debris and unit in need of cleaning. Cleaned filter and ran through chemical cleaning. Cleaned adjacent Oasis units filter also on 2/28/24 in Frisco Texas. Near Main Street Frisco, Texas 75034 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]
Condenser Fan Gave Out
Condenser fan gave out causing the unit to kick out on thermal overload. I had the fan motor in van so I replaced and returned to service on 2/27/24 in Allen Texas. Near EAST Stacey rd. Allen, Texas 75002 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]
Unit Was Not Making Ice When I Arrived
Unit was not making ice when I arrived. I noticed some boxes stacked on the unit next to the ice machine blocking airflow to the condenser. I removed the boxes and the pressure dropped to near 315psi. This is still high so I checked the condenser coil and found it very dirty. I blew it […]
Disassembled Machine Cleaned and Sanitized
Disassembled machine cleaned and sanitized according to manufacturer specs. Will need to return with filter. Customer would like a 6 month Preventative maintenance Contract on 2/23/24 in Balch Springs Texas. Near Seagoville Rd Balch Springs, Texas 75180 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]
Filter Replacement
Filter replacement, change filter on Elkay bottle station 2/21/24 in Coppell Texas. Near State Hwy 121 Coppell, Texas 75019 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]
Installed Condenser Fan Control
Installed condenser fan control. Set accordingly to 225-95 on 2/19/24 in Denton Texas. Near N Masah Branch Rd Denton, Texas 76207 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]
The Compressor was Extremely Hot
The compressor was extremely hot. The unit was so covered in dust and dirt I could not initially tell it was blue. I cleaned unit removing all dirt and debris and could immediately tell that air was moving more freely. The unit started to cool right away. Confirmed the temp was headed in the right […]
Temperature Sensor was not Installed Properly
Temperature sensor was not installed properly. I used my heat gun to melt the ice and reinstalled the temperature sensor between the evaporator fins. I put the unit back together and turned it back on and watched the system cycle to setpoint and differential as it should on 2/9/24 in Irving Texas. Near W Walnut […]
Door Gasket Replacement
Door Gasket Replacement. Remove old and install new gaskets on four doors on 2/7/24 in Dallas Texas. Near Greenville Ave Dallas, Texas 75206 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]
Repaired Condensation Drain Lines That Were Broken
Repaired Diamond Plate Flooring on one corner where the diamond plate pops up on 1/31/24 in Dallas Texas. Near N Westmoreland Rd Dallas, Texas 75211 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]