Cleaned Condenser Coil because the Head Pressure was High
On 6/27/2023 System was cycling off after 5 minutes, I cleaned condenser coil because the head pressure was high, the pressure went down in Mesquite Texas. Near North Belt Line Road Mesquite, Texas 75182 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer]
Deep Cleaned it With Heavy Sanitizer
On 6/23/2023 System was extremely dirty so I took it apart and deep cleaned it with heavy sanitizer/descaler. I also noticed the water flow through the filter was reversed. Customer had extra length of hose some i was able to put it right. I put it back together and ran the machine through a descale […]
Replaced with High Pressure Switch
On 6/21/2023 I recovered all the refrigerant from both stages of the system. I removed the low-pressure switch that was placed on the high side and replaced with high pressure switch and wired it in correctly. I pulled a deep vacuum on both stages. And charged them with 407c in Dallas Texas. Near Lyndon B […]
Replaced the Expansion Valve and Confirmed
On 6/15/2023 I cycled the system when I arrived and found a high head pressure. I cleaned the condenser by blowing it out with nitrogen. The head pressure came down but the over all pressure was low. I added some refrigerant and cycled the system multiple times only to find it was making ice on […]
Supera Single Door Freezer at -4 on Arrival
6/13/2023 Found Supera single door freezer at -4 on arrival. Customer stated it got to -14. Set point at -8 with 6 degree differential. Reset controls to 2 degrees. Checked drain heater, working. Checked evap and condenser, working. Sure low setting caused insulation to be saturated and frozen. Insulation now back to correct state. Gaskets […]
Solenoid Coil was a 208V Coil and the System Required a 120
6/8/2023 I noticed the solenoid coil was a 208V coil and the system required a 120. I went to go get the replacement and installed it and confirmed the system was working as it should in Plano Texas. Near W Park Blvd Plano, Texas 75093 Check out the Areas We Serve and jobs we are […]
Unit Had a Blown Gear Motor Fuse
6/5/2023 Unit had a blown gear motor fuse took me some time to find a replacement. I replaced the fuse. I pulled an amp draw on all electrical components and found them well within specs in Irving Texas. Near N Union Bower Rd Irving, Texas 75061 Check out the Areas We Serve and jobs we […]