Found that the Condenser Coil was Very Dirty

On 5/26/2023 found the unit to be at 34 degrees, checked the condenser and found that the condenser coil was very dirty, causing the unit to run warmer when the ambient temperature rises. I cleaned the coil and restored proper air flow through condenser. Unit was at 34 degrees, no further issues found at this […]

Replaced the Defrost Timer on the Condenser

On 5/25/2023 Replaced the defrost timer on the condenser with a 208v new clock in DESOTO Texas. Near Falcon Dr DESOTO, Texas 75115 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Found a Leak on the Fan Cycling Switch

On 5/24/20023 found the unit to be low on refrigerant, I found a leak on the fan cycling switch off the high pressure gas line, I tightened fitting and stopped leak, continued leak checking with a electronic, and visual bubbles, no other leaks found, I charged unit with 2lbs of R404A, unit dumped 3 batches […]

Discharge ROTOLOK Fitting had Vibrated Loose

On 5/23/2023 started leak checking the Evaporator with electronic detector, no hits inside walk in, proceeded to condenser and found the discharge ROTOLOK fitting had vibrated loose and was leaking, I tightened the fitting and stopped the leak, I did find a small leak on the txv valve pick up screen that I tightened also, […]

Replaced Thermostat with a Mechanical Thermostat

On 5/22/2023 checked the condenser and found unit was off, tested thermostat and found it to be bad, the stat would not adjust at all, replaced thermostat with a mechanical thermostat, unit pulled down to -10 without an issue in Richardson Texas. Near Kas Dr Richardson, Texas 75081 Check out the Areas We Serve and […]

Replaced Valve Plates

On 5/18/2023 Replaced valve plates on the first compressor, (high) upon getting the high compressor going I got the low compressor to come on and found that it had bad valve plates also, picked up new valve plates and installed. No further issues found at this time in Addison Texas. Near Arapaho Road Addison, Texas […]

Replaced a 40amp Contactor 208v

On 5/17/2023 upon investigation of the cooler I replaced a 40amp contactor 208v control and found the unit was wired improperly, wired unit properly and checked all proper operations. Unit is making temperature now in DESOTO Texas. Near Falcon Dr DESOTO, Texas 75115 Check out the Areas We Serve and jobs we are doing by […]

reset the controller and went through set up

On 5/11/2023 reset the controller and went through set up, before it wouldn’t adjust over 28degrees so product was constantly freezing, I took out the parameters and reset up controller to be adjustable like the cooler next to it, it is now set to 35 and store can adjust accordingly from 40 degrees to 32, […]

I Replaced Fan Motor

On 5/10/2023 I could see fan motor trying to move but it would go. I replaced fan motor and watched it start dropping into range in Rockwall Texas. Near Champions Dr Rockwall, Texas 75087 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]

Drain Line Had Been Knocked Off its Supports

On 5/9/2023 Drain line had been knocked off its supports and was drain on the roof. I set them back up and reconnected the drain to drain the city line. I also changed the filters per our usual filter pm in Frisco Texas. Near W Stonebrook Pkwy Frisco, Texas 75034 Check out the Areas We […]