Replaced Condenser Motor in Plano Texas
On 12/30/2022 Checked true refrigerator. Found that the condenser motor bearings were bad. Replaced condenser motor. Checked operation in Plano Texas. Near Sebring Drive Plano, Texas 75023 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]
Rinsed and Cleaned the Dirty Condenser Filter
On 12/22/2022 Ice machine was running when I arrived. Had long harvest error likely cause by the dirty condenser filter. I rinsed and cleaned the dirty condenser filter with water and reinstalled. Machine consistently made ice between 12-15 minutes several times in Dallas Texas. Near N US 75-Central Expy 1000 Dallas, Texas 75243 Check out […]
Cleaned and Adjusted Ice Thickness Probe
On 12/20/2022 Checked ice machine. Found an alert that the water probe was at fault. Pulled water probe out and saw it was heavily scaled up. I cleaned and adjusted ice thickness probe, soaked it in nickel safe ice machine cleaner and wipe all dirt and scale off. Reinstalled water probe. While checking out the […]
Replaced Capacitor on Walk In Cooler
On 12/19/2022 Checked walk-in cooler. When I first got on the roof the condenser was working normally. When the system cycled off and cycled back on the condenser was having trouble starting. Checked capacitor, found that it was bad. Replaced capacitor on walk in cooler and checked operation. Let the system cycle off and back […]
Condenser Coil on Prep Table was Plugged With Dirt
On 12/16/2022 Checked prep table refrigerator. Found that the back of the unit was producing a lot of heat. Found that the condenser coil on Prep Table was plugged with dirt. Cleaned condenser and waited until temperature came down to set point in Dallas Texas. Near Dallas Pkwy Dallas, Texas 75240 Check out the Areas […]
Changed Filter Dryer
On 12/06/2022 Completed a de-scaling of ice machine. When attempted to clean ice machine the refrigerant was not flowing causing the compressor the shut down on low pressure. Notice the filter drier was frosty at the bottom. Recovered Freon out of system. Changed filter drier. Recharged system in Plano Texas. Near W Park Blvd Plano, […]
Replaced Condenser Motor
On 12/05/2022 Checked walk-in cooler. Found that cooler was not temping correctly. Went on roof and put gauges on the condenser. Found that it was cutting out on high head pressure due to the condenser motor not working. Acquired motor from supply house. Replaced condenser motor and checked operation. Cooler is working properly in Frisco […]
Replaced Chiller Saddle Tap Installed on Suction Line
On 12/02/2022 Checked wine chiller. Found that a saddle tap was installed on the suction line. Tap was leaking with the set screw all the way now. Removed saddle tap and added a tap that has to be wielded in. Pulled vacuum on unit and added the appropriate amount of r134a in Frisco Texas. Near […]
Repaired Leak on Copper Line
On 12/01/2022 I Checked a walk-in freezer and found that it was low on Freon. I completed a leak check and found a leak on the copper line. I repaired the leak and Added 5 lbs. of R404a. I Waited until freezer had dropped down to the set point in Frisco Texas. Near Lebanon rd […]
Replaced a Bad Condenser Fan Motor
On 11/30/2022 We replaced a bad condenser fan motor and removed an unnecessary defrost time that had also failed in Haslet Texas. Near Santa Fe Court Haslet, Texas 76052 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerationone.com/areas-we-serve/ [spacer]